Boiler Rental
| Agency | Department of Veterans Affairs |
| Contracting office | 242-network Contract Office 02 (36c242) |
| Place of performance | Montrose, NY |
| Type of notice | Open for bids |
| Set-aside | None, open to all businesses |
| Response deadline | Oct 21, 2026 |
| Posted | Oct 20, 2026 |
| Solicitation number | 36C24227Q0042 |
| NAICS code | 238220, Plumbing, Heating, and Air-Conditioning Contractors |
Summary from the notice
36C24227Q0042 Mod 2 Answers to questions submitted: Q1: What is the observed historical peak steam load of the facility? A1: 120,000 lb./hr. Q2: Will the Montrose VAMC waive the requirements of the VHA Safety Device and Testing Manual? A2: No. Q3: Air permits for emissions are the responsibility of the entity operating/generating the emission, not the owner of the equipment. Please clarify. A3: VA only, not the vendor. Q4: Will the VA change the 9PPM NOx requirement to 30 PPM? A4: No. Q5: Please clarify the size of the Boiler. A5: 800 HP Q6: Will fuel for the rental boiler be furnished by the Government of the Contractor? A6: Government Q7: Confirm intended placement and connection routing if boiler placement is on the south end but connections are at the north end? A7: East side of the plant (end near Boiler 1 near Building 24 hazmat storage area) Q8: What is the required installation and ready for service date? A8: Installation 11/1/2026. Ready for service 12/1/2026. Q9. Is a rental unit rated at about 30ppm NOx on natural gas acceptable for the temporary heating period, given that it is a temporary rental operating under the facility s existing permit? A9. Yes Q10. If 9 ppm NOx is mandatory, will the Government accept a unit fitted with flue gas recirculation (FGR) or selective catalytic reduction (SCR) to meet it, and will any additional time be allowed for delivery? A10. The most important factor is that the vendor make the delivery date, so the 9-ppm cis is not a deal b…
Other open NAICS 238220 notices
| Deadline | Notice | Set-aside |
|---|---|---|
| Oct 21 Closes today |
Two sets of HVAC units or Mobile Ground Control Station
National Aeronautics and Space Administration, Edwards, CA |
Small business |
| Oct 22 1 day left |
Troubleshoot & Repair of Portable Chillers Service Requirement
Department of the Air Force, JBSA Lackland, TX |
Small business |
| Oct 23 2 days left |
FMC Devens - Replace Boiler Burners (3) Project 26Z2BF8
Federal Prison System / Bureau of Prisons, Ayer, MA |
Small business |
| Oct 23 2 days left |
Reverse Osmosis System Modifications
Department of Veterans Affairs, Minneapolis, MN |
Open to all |
| Oct 23 2 days left |
TVHS AC VRF System Installation
Department of Veterans Affairs, Nashville, TN |
SDVOSB |
| Oct 23 2 days left |
HVAC Repair JV Resource_jordan Valley
Bureau of Land Management |
Small business |
Details copied from the public SAM.gov notice. BidFox is not connected to SAM.gov or the U.S. Government, so check the official notice before you bid.