Renovate HVAC Building 2007

Closed Pre-solicitation WOSB set-aside NAICS 238220
AgencyDepartment of Defense
Department of the Air Force
Contracting officeFa3016 502 Cons Cl
Place of performanceSan Antonio, TX
Type of noticePre-solicitation
Set-asideSBA Certified Women-Owned Small Business (WOSB) Program Set-Aside (FAR 19.15)
Response deadlineSep 13, 2017
PostedSep 8, 2017
Solicitation numberFA3016-17-R-0091
NAICS code238220, Plumbing, Heating, and Air-Conditioning Contractors

Read the official notice on SAM.gov

Summary from the notice

Question: Revised Section 01 11 00 paragraph 1.4.b states, "The Noise Criterion (NC) for the project area within the building is 35db. All new VAV and air side units shall be attenuated such that all new and interdicted ductwork and the balanced air flow shall meet the NC." Does the Government require maximum 35dB or NC35 for Room 119C? In our opinion, limiting the Contractor to straight 35dB across all frequencies is not feasible for this project. The following highlights the difference between "dB" levels and "NC" ratings: Noise Criterion (NC) were established in the U.S. for rating indoor noise like noise from air-conditioning equipment and similar. In Europe it is common to use the Noise Rating Curve - NR <http://www.engineeringtoolbox.com/nr-noise-rating-d_60.html> . The method consists of a set of criteria curves ranging 63 to 8000 Hz and a tangency rating procedure. The criteria curves defines the limits of octave band spectra that must not be exceeded to meet the occupants acceptance in the actual spaces. The NC rating can be determined by plotting the octave band levels for a given noise spectrum - the NC curves. The noise spectrum is specified as having a NC rating same as the lowest NC curve which is not exceeded by the spectrum. Answer: Noise level is acceptable 35db to 40db or acceptable levels as per office building industry standards.

Other open NAICS 238220 notices

DeadlineNoticeSet-aside
Oct 20
Closes today
Chiller Compressor Replacement at the Edward Hines Jr. VA Hospital (Hines) Building 228
Department of Veterans Affairs, Hines, IL Sources sought
Open to all
Oct 20
Closes today
CAS Education Heat Pump
Forest Service, Ozark, AR
Small business
Oct 20
Closes today
FMC Devens - Replace Boiler Burners (3) Project 26Z2BF8
Federal Prison System / Bureau of Prisons, Ayer, MA
Small business
Oct 20
Closes today
Green Mountain National Forest Storage tank cleaning and inspection at Hapgood Pond
Forest Service, Peru, VT
Small business
Oct 20
Closes today
IDIQ, Joc for Plumbing, Heating, Air Conditioning Projects at Marine Corps Logistics Base Barstow, Marine Corps Air-ground Combat Center 29 Palms, Marine Corps Mountain Warfare Training Center Bridgeport, and Naval Air Weapons Station China Lake, Ca Aor
Department of the Navy
Small business
Oct 20
Closes today
Chillers and Cooling Towers Repairs
Department of Veterans Affairs Special notice
Open to all

Details copied from the public SAM.gov notice. BidFox is not connected to SAM.gov or the U.S. Government, so check the official notice before you bid.